Maintenance records are worth keeping only if you can use them. A good record answers three questions fast: what was done, what was found, and what changed since last time.
What to record every visit
- Equipment ID and location.
- Date and who did the work.
- The task performed.
- Readings taken, such as supply and return temperature, motor amps, filter pressure drop and static pressure.
- Parts replaced, with part numbers.
- Findings and recommendations.
- Photos, when something is damaged or unusual.
A simple log format
| Date | Unit | Task | Readings | Findings | Tech |
|---|---|---|---|---|---|
| 2026-03-12 | RTU-3 | Filter change | Filter drop 0.9 in. w.g. before, 0.2 after | Belt cracked, replaced | Initials |
The row above is a format example only. The point is that each row is short and has numbers in it.
Why the readings matter
A note that says “unit running fine” is no help in a year. A note that says “motor 11.2 amps, nameplate 12.5” shows a trend. Start from the readings in your TAB report, which records how the system performed when it was new. Compare every later reading to that baseline.
What good records let you do
- Troubleshoot faster, because you can see what changed.
- Support a warranty claim, with proof that maintenance was done.
- Answer an inspector, with documents instead of memory.
- Plan replacements, by seeing which units cost the most to keep running.
The same habit applies to testing: see why to document HVAC testing and adjustments.
Pick a system your team will actually use
Use whatever your team will actually fill in. A maintenance software system helps at scale, but a spreadsheet with a row per visit works. Decide who owns the log, and where it lives, and keep it for the life of the equipment.
Common mistakes
- Records scattered across texts and notebooks. Pick one place and use it.
- No unit IDs. “The rooftop unit” does not tell anyone which one.
- Only logging failures. Routine visits with good readings are the baseline you need.
- No owner for the log. Someone has to check that entries are being made.
A five-minute habit for technicians
Before leaving a unit, the technician records three readings, one finding and one recommendation. That takes five minutes, and over a year it builds a history of every machine. It also means that when a technician leaves, the knowledge stays.
Pick a system your team will actually use
A maintenance management system helps when you have many buildings or many technicians. For one building, a spreadsheet with a row per visit is enough, as long as everyone uses it. Whatever you choose, test it by asking one question: could a new technician find the last three entries for a unit in under a minute?
Questions facility managers ask about maintenance records
Do we need maintenance software?
Not to start. Software helps with reminders, parts and cost tracking at scale. A consistent habit matters more than the tool.
How long should we keep records?
For the life of the equipment at least, and longer where a warranty, insurer or regulation asks for it. Keep the original TAB report with them.
Which readings are most useful?
Supply and return air temperature, motor amps, static pressure and filter pressure drop. They are quick to take and they show change before failure.
Related reading: The Link Between Proper HVAC Installation and Building Longevity.
To start your records from a measured baseline, call Ghazi Hussain at (908) 323-9780.
Related Posts
- The Impact of Mold on Indoor Air and How to Address It
- How Government Agencies Can Transition to Sustainable HVAC Systems
- The Economic Benefits of Energy-Efficient HVAC Systems for Contractors
- How to Reduce Energy Costs with Routine HVAC Inspections
- How to Identify and Eliminate Common Indoor Air Pollutants
- How to Prepare Your Home for Seasonal Air Quality Challenges
- The Economic Benefits of Proper HVAC Testing for Contractors
- The Role of Air Filtration in Protecting Against Airborne Contaminants