Temperature imbalances troubleshooting

Best Practices for Troubleshooting Temperature Imbalances

A temperature imbalance means one space is out of step with the rest of the building. The cause is usually in the air, the controls or the room itself. Work through them in order, and measure at each step.

Causes to check

  • Airflow. The room gets more or less air than the design intends.
  • Thermostat. It reads wrong or sits in the wrong place.
  • Loads. Sun, equipment or crowding add heat the design did not expect.
  • Return path. A closed door with no return opening can pressurize the room and cut supply air.
  • Reheat and dampers. A valve or damper that is stuck or set wrong.
  • Stratification. Warm air collects high in tall rooms.

Symptom table

SymptomCheck first
Hot only in the afternoonSolar gain, maximum airflow to the zone
Cold in one room, fine elsewhereAirflow above design, reheat valve, minimum airflow setting
Hot in a room with the door shutReturn path, transfer air
Thermostat reads fine but people disagreeSensor location and calibration
Hot or cold upstairs, opposite downstairsStack effect, zoning, airflow balance between floors

A step-by-step method

  1. Log temperature in the room for a few days.
  2. Measure supply airflow at the room’s outlets and compare with design.
  3. Check the thermostat against a reference thermometer.
  4. Check the zone damper, reheat valve and controller.
  5. Look at the return path.
  6. Change one thing, then log again.

For related reading, see temperature imbalances in large buildings and diagnosing airflow problems.

Common mistakes

  • Adjusting the thermostat setpoint. It hides the cause and costs energy.
  • Closing a damper in a cold room without checking. That may push the problem somewhere else.
  • Ignoring the return. Supply gets all the attention, but a blocked return stops airflow too.

Questions contractors ask about temperature imbalances

Is it ever the building and not the system?

Yes. Added equipment, a change of use or a window film can change the load. If the load changed, the system may need to be re-balanced or resized for the room.

How much airflow difference matters?

Compare to the spec’s tolerance. A common figure is about 10 percent of design, but follow the project documents.

Will balancing solve it?

If airflow is the cause, yes. If the load or the controls are the cause, it will not, and measuring tells you which.

Common fixes, and how much effort each takes

FixEffortUse when
Move or recalibrate a thermostatLowReading disagrees with a reference thermometer
Adjust a balancing damperLow to mediumBranch airflow is off design and others are on design
Add or enlarge a return pathMediumRoom is pressurized with the door closed
Reset VAV box minimum or maximumLow to mediumReheat is running a lot, or the box cannot meet peak load
Change a diffuser typeMediumThrow or pattern is wrong for the room
Re-zone or add a zoneHighLoads in one zone differ too much to share a thermostat

Document the fix

After any change, record the before and after readings and what you changed. If you adjusted a damper, mark its new position and lock it. The mark helps the next person see when something has moved.