How Healthcare Facilities Can Prepare for Seasonal HVAC Demands

Hospitals run all year, with strict limits on temperature, humidity and pressure. The seasons push against those limits: humid summers strain cooling and dehumidification, and cold winters strain heating, preheat and humidification. This guide covers the seasonal checks.

What changes with the season

SeasonStress on the systemChecks
SummerHigh humidity and cooling load, long hours at peakDehumidification capacity, chilled water supply, coil cleanliness, drain pans
FallMixed conditions and simultaneous demand for heating and coolingControls changeover, economizer where used, reheat
WinterCold outdoor air, low indoor humidity, freeze riskPreheat coils, freeze protection, humidifier operation and cleanliness
SpringPollen and swings in temperatureFilters, outdoor air, controls

Humidity ranges matter

ASHRAE/ASHE 170 sets design temperature and humidity ranges by space type. Operating rooms, for example, have a design range for relative humidity that is neither too dry nor too damp. Humidity that strays outside the range affects comfort, equipment and infection control. Check the ranges for each space type in the edition your facility follows.

A seasonal checklist for facilities teams

  1. Verify heating and cooling plant capacity before the season starts.
  2. Test freeze protection on every coil that sees outdoor air.
  3. Clean coils and drain pans, and inspect humidifiers.
  4. Check pressure relationships in critical rooms after the changeover.
  5. Measure airflow in critical rooms and compare with design.
  6. Test backup power for ventilation equipment. See why healthcare HVAC needs emergency power.

For the underlying room requirements, see healthcare HVAC for patient safety and air balancing in healthcare.

Outdoor air and the season

Outdoor air makes up a big share of a hospital’s heating and cooling load, because the ventilation rates are high. In humid summer weather it carries moisture that must be removed. In winter it needs heating, and sometimes humidification. Energy recovery can reduce that load, but only if supply and exhaust airflows stay balanced.

Common mistakes

  • Waiting for the first cold night. Test freeze protection beforehand.
  • Treating humidity as a comfort issue only. It affects equipment and infection control.
  • Skipping post-changeover checks. Pressure relationships can move.

Questions hospital teams ask about seasonal HVAC

How often should critical rooms be checked?

At least at each seasonal changeover, plus after any change to the system, and as often as your policy and accreditation require.

Who should do the checks?

Your engineers for the plant and controls, and a balancer with healthcare experience for airflow and pressure.

What if a room drifts out of range?

Treat it as a deficiency, find the cause, correct it and retest. Report it as your procedures require.

A worked example of a summer humidity drift

Suppose a hospital’s recovery area drifts above its humidity range during a heat wave. Trend data shows the cooling coil leaving air temperature rising and the outdoor air damper at a higher position than normal. A check finds a coil partly fouled and a minimum outdoor air setting above the design value. Cleaning the coil, resetting the damper from a measured airflow and re-checking pressure relationships brings the room back into range. A log of the readings before and after goes in the file. The sequence, trend then measure then fix then verify, is the useful part.

Related reading: Seasonal Air Quality Checks for Commercial Buildings, How to Handle Seasonal HVAC Challenges: Summer and Winter Tips and How Educational Institutions Can Address Seasonal HVAC Challenges.

To test critical rooms before the season changes, call Ghazi Hussain at (908) 323-9780 for a quote.

Need Help?

Ghazi-Hussain-Air-Balance-Masters