Seasonal HVAC Challenges

How to Handle Seasonal HVAC Challenges: Summer and Winter Tips

HVAC systems face different stress in each season. A few checks before each one prevent most seasonal failures. Use this as a checklist, and adjust it to your equipment.

Before summer

  • Clean condenser and evaporator coils.
  • Clear condensate drains and test the drain pans.
  • Check refrigerant circuits, by a licensed technician.
  • Test cooling controls and setpoints.
  • Confirm the economizer changes over at the right outdoor conditions.
  • Check humidity control. Overcooled, damp air leads to mold complaints.

Before winter

  • Inspect heating coils, burners or boilers.
  • Test freeze protection on coils that see outdoor air, including freezestats and outdoor air damper closure.
  • Check that outdoor air dampers close tight, so cold air does not leak in.
  • Check the humidifier, if there is one, and its controls.
  • Test heating controls and setback schedules.

In the shoulder seasons

Spring and fall are when systems waste the most. Mild weather means a building can need heat in one zone and cooling in another, and a poorly set system does both at once. Check for simultaneous heating and cooling, and confirm the economizer is using outdoor air when it should.

What usually fails

SeasonCommon failureEarly sign
SummerBlocked condensate drainWater at the unit or in the ceiling
SummerFouled coilWarm supply air, long run times
WinterFrozen coilFreezestat trips, low supply air temperature
WinterLeaking outdoor air damperCold spots near the unit
ShoulderStuck economizerCompressor runs on a mild day

After a seasonal change, check airflow too. Seasonal airflow adjustments explains when and why to adjust. For other building types, see schools and healthcare facilities.

Common mistakes

  • Starting cooling without testing the economizer. A stuck damper wastes energy all summer.
  • Letting the freeze protection go untested. A frozen coil can burst and flood the unit.
  • Leaving heating and cooling both enabled in shoulder weather. They fight each other.
  • Forgetting the outdoor air. Winter and summer outdoor air loads change how much energy ventilation costs.

Plan it as a calendar

Put the two seasonal checklists on the calendar eight weeks ahead, so parts and contractors are lined up before the first hot or cold week. Record what you find, then compare year over year. A coil that needs cleaning every spring is a pattern, and the log shows it. See how to build a preventative maintenance program.

Questions facility managers ask about seasonal HVAC

When should we switch from heating to cooling?

Do not do it by hand on a fixed date. Let the controls decide from outdoor conditions, and check that heating and cooling cannot run against each other. Manual changeovers are how both end up enabled in shoulder weather.

Do we need freeze protection in a mild climate?

If any coil sees outdoor air that can drop below freezing, yes. A single cold night is enough to freeze a coil with no protection. Test the freezestat and the damper closure before the cold season.

How early should we start seasonal prep?

About eight weeks before the season changes. That is enough time to order parts and book contractors.

Related reading: Seasonal Air Quality Checks for Commercial Buildings, Top 10 HVAC Maintenance Tips for Facility Managers and Best Practices for Maintaining HVAC Systems in Schools.

To check that your system delivers design airflow before the season turns, call Ghazi Hussain at (908) 323-9780.

Need Help?

Ghazi-Hussain-Air-Balance-Masters