HVAC troubleshooting

How to Troubleshoot Common HVAC Problems in Large Buildings

In a large building, a problem in one room can come from a fan, a duct, a valve or a control. Guessing wastes days. A fixed method saves time because it narrows the cause step by step.

A fixed method to find the cause

  1. Define the symptom. Where, when, how often and who reports it.
  2. Look at the trend data. Pull the controls trend logs for the equipment serving the area. Look for what changed on the day the problem began.
  3. Check the basics. Power, controls status, filters, belts, valves and dampers.
  4. Measure. Airflow at the outlets, static pressure in the duct, supply and return temperatures, and water flow on hydronic systems.
  5. Compare with design. The TAB report gives you the numbers the system was balanced to.
  6. Isolate. Change one thing, observe, and record the result.

Symptom to likely cause

SymptomCommon causes
Room too warm in cooling seasonLow airflow, closed or stuck damper, failed reheat valve, thermostat error
Room too coldToo much airflow, reheat not working, minimum airflow set too high
Whole floor warmChilled water or cooling coil problem, air handler fan or filter, controls
Noise at outletsHigh velocity, damper partly closed, loose components
Doors hard to open or whistlingBuilding pressure out of range from supply and exhaust imbalance
High static pressureLoaded filters, closed dampers, duct restriction
Low temperature rise on chilled waterValve or coil issues, too much flow

Large-building issues that small ones do not have

  • Building pressure. Exhaust, return and outdoor air have to be balanced, or doors and elevator shafts show it.
  • Zone interaction. One starved zone can drag a whole system. See why multi-zone systems need balancing.
  • Stratification. Warm air collects high in tall spaces.
  • Distribution on long runs. Pressure losses reduce airflow at the far end.

For more on diagnosing airflow, see our guide to airflow problems and common air balance issues.

Questions building engineers ask about troubleshooting

Where do I start when I have no baseline?

Measure now. Record airflow, pressures and temperatures at the affected areas and the equipment serving them. That becomes the baseline for the next problem.

Should I change settings while I investigate?

Change one thing at a time, write down what you changed and when, and put it back if it did not help. Otherwise you cannot tell what worked.

When should I bring in a balancer?

When airflow is the suspect and you need instruments and a method to prove it, or when several zones have different complaints at once.

Keep a troubleshooting log

Write one line for each step: what you checked, what you measured, what you changed and what happened. A log has three uses. It stops you repeating a step. It helps the next person pick up the problem. And it becomes a record of how this building behaves.

Common mistakes

  • Swapping parts before measuring. A new actuator on a good damper fixes nothing.
  • Trusting the controls screen. It shows commands and sensor readings, which can be wrong.
  • Changing several things at once. You cannot tell which one worked.
  • Not comparing with design. A reading means little without the number it should have been.

Related reading: How to Troubleshoot Common HVAC Issues During Construction.

To have a problem system measured, call Ghazi Hussain at (908) 323-9780 for a quote.

Need Help?

Ghazi-Hussain-Air-Balance-Masters