HVAC system metrics

Key Metrics HVAC Contractors Should Monitor During System Testing

Testing produces a lot of numbers. A few of them tell you whether the system is healthy. This guide lists those, what each reveals, and how to read them against design.

The metrics that matter

MetricWhat it tells you
Airflow at each outlet, as a percentage of designWhether each space gets the air it was designed for
Total airflow at the fanWhether the system moves the design volume
Static pressure across filter, coil and fanWhere the system is restricted, and how hard the fan works
Fan speed (RPM)Whether the fan runs where it was designed to run
Motor amps and voltageWhether the motor is loaded as expected
Supply, return and mixed air temperatureWhether coils and controls are working
Outdoor air quantity or percentageWhether ventilation meets design
Room pressure relationshipsWhether air moves the intended direction
Water flow and pressure drop, on hydronic systemsWhether coils get their design flow

How to read them

  • Compare each reading with design. The number means little alone.
  • Look at the tolerance in the spec. A common figure is plus or minus 10 percent of design, but check your own documents.
  • Read the set together. High static pressure with low airflow points to a restriction. Low airflow with low pressure points to the fan or a leak.
  • Record conditions. Note filter state, damper positions and any overrides at the time.

See what TAB measures and how to read the graphs in a TAB report.

Common mistakes

  • Measuring only airflow. Pressure and amps explain why airflow is off.
  • Taking one reading. Repeat and average where the flow is unsteady.
  • Not recording conditions. A reading with a loaded filter is not a baseline.

Questions contractors ask about testing metrics

Which reading should I trust most?

Those taken with calibrated instruments by a method suited to the location, such as a traverse in a straight duct or a hood at an outlet.

What if readings are within tolerance but there are complaints?

Check the controls, the load and the thermostat. Airflow can be right while the room is still uncomfortable.

Where should I keep the numbers?

In the TAB report, and in the maintenance log as the baseline for later readings. See how to document maintenance.

A sample acceptance table

OutletDesign (cfm)Measured (cfm)Percent of designResult
Format example onlyValue from drawingsValue from hoodMeasured divided by designWithin or outside tolerance

Build the table for every outlet. Rows outside the tolerance become the deficiency list, and the rest become the proof that the system delivers.

How to present results to an owner

  1. Start with the headline: how many outlets are within tolerance.
  2. List the exceptions and what is being done about each.
  3. Show the fan data and static pressures in one summary page.
  4. State the outdoor air quantity against design.
  5. Give the owner the baseline to compare with in future years.