A test you cannot show is a test the inspector will repeat. Good records protect the contractor, help the owner and give the next technician somewhere to start. This guide covers what to record and how to keep it.
What to record
| Item | Details to include |
|---|---|
| Equipment | ID, location, model, serial and nameplate data |
| Airflow | Design and measured values at each outlet and at the fan |
| Pressures | Static pressure across filters, coils and fans, and in ducts |
| Fan and motor | RPM, amps, volts, and any sheave or drive changes |
| Temperatures | Supply, return, mixed and outdoor air |
| Adjustments | What was changed, from and to values, and damper positions |
| Instruments | Model, serial and calibration date |
| Conditions | Date, time, weather, filter condition, overrides |
Keep a change log
Every adjustment should have a line: who changed what, when and why. If a damper was moved, mark its new position and lock it. A change log solves most arguments about whether a system was left at the right setting.
Organize the records
- Name files by system and date, so they sort.
- Keep one folder per project, with the report, instrument certificates and photos.
- Photograph dampers, nameplates and any deficiencies.
- Give the owner a copy, and keep your own.
- Retain records for as long as the contract and your insurer require.
See what a finished report contains in the essential components of an air balance report and how the TAB report is used in construction.
Who needs the records
- The owner, as a baseline for maintenance.
- The inspector, as proof of compliance.
- The commissioning agent, to verify performance.
- Future technicians, to troubleshoot with the original numbers.
Common mistakes
- Recording only final numbers. The starting readings show what changed.
- Leaving out units. A number with no unit is a guess.
- Losing the calibration certificate. Without it, the readings can be challenged.
Questions contractors ask about testing records
Do I need photos?
They help. A photo of a damper position or a nameplate settles questions a number cannot.
How long should I keep records?
For the life of the warranty at least, and longer if your contract or insurer asks. Digital storage makes this cheap.
Should records be digital?
A digital copy is easier to share and search. A signed paper copy may still be required by the spec.
A record sheet you can adapt
| Field | Example entry |
|---|---|
| System | AHU-1, supply fan |
| Date and conditions | Date, time, filters installed, no overrides |
| Before | Fan RPM, airflow, static pressure |
| Change | Sheave changed, damper moved to a new position |
| After | Fan RPM, airflow, static pressure |
| Instrument | Model, serial, calibration date |
| Person | Name and certification |
One sheet per system, filled in at the time, makes the final report quick to write and easy to defend.
To receive a complete record of measured airflow and adjustments, call Ghazi Hussain at (908) 323-9780 for a quote.
Related Posts
- The Economic Benefits of Proper HVAC Testing for Contractors
- How to Choose the Best Air Purifier for Your Needs
- The Link Between Building Design and HVAC System Performance
- Key Metrics HVAC Contractors Should Monitor During System Testing
- The Role of Facility Managers in Improving Indoor Air Quality
- Best Practices for Coordinating HVAC Testing with Project Deadlines
- How to Optimize HVAC Systems for Maximum Energy Efficiency
- How to Troubleshoot Common HVAC Problems in Large Buildings