What to record

ItemDetails to include
EquipmentID, location, model, serial and nameplate data
AirflowDesign and measured values at each outlet and at the fan
PressuresStatic pressure across filters, coils and fans, and in ducts
Fan and motorRPM, amps, volts, and any sheave or drive changes
TemperaturesSupply, return, mixed and outdoor air
AdjustmentsWhat was changed, from and to values, and damper positions
InstrumentsModel, serial and calibration date
ConditionsDate, time, weather, filter condition, overrides

Keep a change log

Every adjustment should have a line: who changed what, when and why. If a damper was moved, mark its new position and lock it. A change log solves most arguments about whether a system was left at the right setting.

Organize the records

  1. Name files by system and date, so they sort.
  2. Keep one folder per project, with the report, instrument certificates and photos.
  3. Photograph dampers, nameplates and any deficiencies.
  4. Give the owner a copy, and keep your own.
  5. Retain records for as long as the contract and your insurer require.

See what a finished report contains in the essential components of an air balance report and how the TAB report is used in construction.

Who needs the records

  • The owner, as a baseline for maintenance.
  • The inspector, as proof of compliance.
  • The commissioning agent, to verify performance.
  • Future technicians, to troubleshoot with the original numbers.

Common mistakes

  • Recording only final numbers. The starting readings show what changed.
  • Leaving out units. A number with no unit is a guess.
  • Losing the calibration certificate. Without it, the readings can be challenged.

Questions contractors ask about testing records

Do I need photos?

They help. A photo of a damper position or a nameplate settles questions a number cannot.

How long should I keep records?

For the life of the warranty at least, and longer if your contract or insurer asks. Digital storage makes this cheap.

Should records be digital?

A digital copy is easier to share and search. A signed paper copy may still be required by the spec.

A record sheet you can adapt

FieldExample entry
SystemAHU-1, supply fan
Date and conditionsDate, time, filters installed, no overrides
BeforeFan RPM, airflow, static pressure
ChangeSheave changed, damper moved to a new position
AfterFan RPM, airflow, static pressure
InstrumentModel, serial, calibration date
PersonName and certification

One sheet per system, filled in at the time, makes the final report quick to write and easy to defend.