Air filtration systems

The Role of Air Filtration in Maintaining Healthy Indoor Spaces

A filter only works if it fits, matches the equipment and gets changed on time. A higher rating does not help if the fan cannot pull air through it. This guide covers how to choose a filter and keep it working.

Understanding MERV ratings

MERV (Minimum Efficiency Reporting Value) is a rating from ASHRAE Standard 52.2 that shows how well a filter captures particles of different sizes. Higher numbers capture smaller particles. As a rough guide, MERV 8 is a common minimum in commercial buildings, and ASHRAE’s epidemic guidance has suggested MERV 13 or better where the system can handle it. HEPA filters, a separate class, capture very small particles and are used where air quality is critical.

The trade-off: efficiency versus airflow

A finer filter resists airflow more. If the fan cannot overcome the added pressure drop, airflow falls, coils can freeze, comfort suffers and energy use rises. Before you upgrade, check the fan’s capacity and the filter housing. After a change, confirm airflow still meets design. That is where air balancing comes in.

Types of filtration

  • Mechanical filters use a physical barrier. Pleated and bag filters are common in air handlers.
  • HEPA filters are a high-efficiency mechanical type, used in critical spaces.
  • Electrostatic filters use an electric charge to attract particles.
  • Gas-phase filters target odors and gases, which particle filters do not stop.
  • Portable air cleaners can add filtration to a space the central system cannot upgrade.

Keeping filters effective

  1. Fit. Seal the frames. Air takes the easy path around a poorly fitted filter.
  2. Pressure drop. Install gauges across each bank and change filters at the manufacturer’s limit.
  3. Record. Note the date, the gauge reading before and after, and the filter type.
  4. Spare stock. Keep the right sizes on hand so changes do not wait.
  5. Review the rating whenever the building’s use or the equipment changes.

For healthcare settings, filtration needs differ. See filtration for healthcare facilities.

Questions facility managers ask about filters

Can we just install MERV 13 everywhere?

Not without checking. Some systems cannot move enough air through it. Test the pressure drop and airflow on one unit first.

Do filters remove odors?

Particle filters do not stop most gases and odors. Gas-phase filters or source control do.

How do we know the filter is the problem?

Measure the pressure drop and the airflow. A high pressure drop with low airflow points to a loaded or undersized filter.

A filter record worth keeping

DateUnitFilter type and sizePressure drop beforePressure drop after
Example rowAHU-2Pleated, 24 x 24 x 4Reading in in. w.g.Reading in in. w.g.

After a few changes you can see how fast each unit loads, and set the interval to match.

Common mistakes

  • Using the wrong size. Gaps around the frame let unfiltered air through.
  • Installing filters backward. The airflow arrow shows the direction.
  • Running filters past their limit. Loaded filters raise energy use and can starve a coil of air.
  • Upgrading the rating without checking the fan. Measure the pressure drop and airflow after the change.

When a filter upgrade needs more than a filter

If the finer filter pushes the fan past its limits, you have three options: a larger filter bank to lower the face velocity, a fan or drive change, or a lower rating. Choose from measured pressure drop and airflow, not from the rating alone.