Ventilation standards tell you how much outdoor air a building has to bring in. Get the number wrong in either direction and you pay for it: too little and occupants complain and the building fails inspection, too much and you heat and cool air you did not need to. This guide shows where the numbers come from, works one example, and explains what testing and balancing checks.
Which standard applies
- ASHRAE Standard 62.1 sets minimum ventilation rates for commercial and institutional buildings. It is the reference most commercial designs use.
- ASHRAE Standard 62.2 covers residential buildings, so it does not apply to commercial work.
- ASHRAE/ASHE Standard 170 covers healthcare facilities and has its own, stricter requirements.
- The International Mechanical Code and local codes. Many jurisdictions enforce ventilation through the mechanical code, and others point to ASHRAE 62.1 directly.
Which edition applies depends on your jurisdiction and the date of the permit. Check with the authority having jurisdiction, and use the project’s design documents as the final word. For background, see the role of ventilation standards in building design and in government buildings.
How the ventilation rate is calculated
In ASHRAE 62.1 the ventilation rate procedure sets the outdoor air a space needs from two parts: an amount per person and an amount per square foot. The formula for the breathing zone is:
Breathing zone outdoor airflow = (people rate × number of people) + (area rate × floor area)
Typical values from the standard’s occupancy table:
| Space | Per person (cfm) | Per square foot (cfm) |
|---|---|---|
| Office | 5 | 0.06 |
| Conference and meeting room | 5 | 0.06 |
| Classroom (ages 9 and up) | 10 | 0.12 |
| Retail sales floor | 7.5 | 0.12 |
| Restaurant dining room | 7.5 | 0.18 |
These values are from ASHRAE 62.1. Confirm them against the edition your project uses.
A worked example
An office of 10,000 square feet with 50 people:
- People: 5 cfm × 50 = 250 cfm
- Area: 0.06 cfm × 10,000 = 600 cfm
- Breathing zone outdoor airflow: 250 + 600 = 850 cfm
The outdoor air the system must actually deliver can be higher than 850. It depends on how well the supply air reaches the breathing zone and how the system shares air between zones, both of which the designer accounts for. Notice also that in this office the floor area, not the people, drives most of the number. Use our air changes per hour calculator and ventilation compliance planner to check numbers on your own spaces.
What testing and balancing checks
Design numbers do nothing until they are measured in the building. A balance for ventilation should verify:
- Outdoor air at the intake. It is measured directly, or worked out from total supply and return airflow.
- Minimum outdoor air position. The damper setting that delivers the design minimum.
- Exhaust airflow in restrooms, kitchens and other exhaust spaces.
- Airflow to each zone against the design.
- Demand-controlled ventilation sensors (CO2 sensors) read correctly where they are used.
See how TAB services prove ventilation compliance.
Common reasons buildings fall short
- The outdoor air damper is stuck closed, or set so far closed that it passes almost nothing.
- Intake louvers or filters are loaded with debris, which cuts the airflow.
- Controls were never set up for the economizer or the minimum outdoor air.
- CO2 sensors are out of calibration, so the system ventilates too little or too much.
- The use of a space changed, but the ventilation did not.
If a building already runs, here is what contractors owe to ventilation standards.
What owners and facilities managers should do
- Keep the design ventilation figures and the latest TAB report on file.
- Re-check ventilation whenever a space changes use or occupancy.
- Keep outdoor air intakes clear and filters on schedule.
- Have outdoor air re-measured after major control or equipment changes.
Related reading: Building Compliance Analyzer for Safety Standards.
Need outdoor air verified in your building? Call Ghazi Hussain at (908) 323-9780 for a quote.
Related Posts
- Best Practices for Coordinating HVAC Testing with Project Deadlines
- The Economic Benefits of Sustainable HVAC System Design
- The Importance of Regular HVAC Testing in Government Buildings
- How to Improve Air Circulation in Older Homes
- The Importance of Air Balancing for HVAC Contractors
- Key Metrics HVAC Contractors Should Monitor During System Testing
- How to Choose the Best Air Purifier for Your Needs
- The Role of HVAC Contractors in Meeting Ventilation Standards